热门搜索: MPR E-Scan在线折光仪卫生级设计食品制药适用 MPR E-Scan在线折光仪 实时数据传输 4-20mA/RS485 MPR E-Scan在线折光仪防爆设计危险工况适用 MPR E-Scan在线折光仪 耐酸碱 强腐蚀工况专用 MPR E-Scan芳烃油在线浓度分析仪防爆型高精度 MPR E-Scan在线橡胶油折光率分析仪高精度免维护 MPR E-Scan在线浓度仪高精度测量尿素浓度 MPR E-Scan高精度测量发烟硫酸浓度 MPR E-Scan在线折光仪测量硫酸浓度 MPR E-ScanEMC公司E-Scan在线氢氧化锂浓度分析仪应用 MPR E-Scan_Double氧化铝溶出液相全分析苛碱氧铝分析仪 氢氧化钾装置MPR E-Scan一次盐水浓度分析仪 MPR E-Scan氢氧化钾装置中在线硫酸浓度分析仪 MPR E-Scan在线浓度仪氢氧化钾装置KOH浓度分析仪 在线氯化铵浓度分析仪双输出无耗材 MPR E-Scan在线浓度仪氢氧化钾装置盐水分析仪

PRODUCT CLASSIFICATION

产品分类

新闻中心/ News Center

您的位置:首页  /  新闻中心  /  纸浆厂黑液回收锅炉在线折光仪三大故障原因分析

纸浆厂黑液回收锅炉在线折光仪三大故障原因分析

更新时间:2018-08-18      浏览次数:1279

The three major causes of refractometer trouble or failure in black liquor recovery boilers are:

Loss of cooling water and its effect on the sensing head.

Lack of reliability of the prism wash.

Condensation in the sensing head.

These may not apply to all refractometers due to differences in construction and circuitry.

Cooling Water Loss

It is of vital importance that the loss of cooling water be detected. This may be done through a temperature sensing element or flow monitor which shuts down the refractometer involved.

Damage to the sensing element of a refractometer does not occur instantaneously, but it is essential that the system detect abnormal temperatures due to cooling water loss, flow blockage, etc., and that the cooling water be promptly restored.

The individual refractometer manufacturer’s instruction and maintenance manuals shall be consulted with reference to: potential damage to the sensing element; identification of a damaged element; how and when to replace a damaged element.

Prism Wash

The time interval between prism washes may vary with the black liquor composition. It is recommended that the minimum wash period be 7-10 seconds of wash every 20 minutes. Short duration washes at more frequent intervals are more effective than long washes at long intervals. Ideally, steam pressure for prism washing should be 35 psig above the black liquor pressure, plus the pressure required to open the protective check valve.

Awareness must be maintained of the effect of changes to the prism wash programming variables. Various refractometer systems have the capability to adjust: condensate drain time, steam on time, recovery time and interval between wash time. It may be possible to configure the system to have the total time that both refractometers are in their wash cycle represent a significant percentage of operating time. If one refractometer is out of service for repairs and the remaining refractometer is in prism wash, black liquor solids are not being monitored. Prism wash should be minimized to that needed to maintain the system.

If high pressure steam is used, it may abrade the prism. If only high pressure steam is available, a reducing valve shall be used.

The refractometer prism must have a clear polished optical surface, and if it becomes abraded, it must be replaced.

If the prism wash system has not operated properly and the prism becomes coated, it must be removed and properly cleaned.

Condensation in Sensing Head

Condensate may build up in the refractometer sensing head and if this occurs, the instrument operation will be erratic.

The procedure for determining this condition and for the elimination of excessive moisture in the sensing head is not the same for all refractometers. The manufacturer’s instruction and maintenance manuals shall be consulted and followed carefully.